Before you start
- Enable Telnet on the PDU and note its Telnet username and password. These are separate from the web interface login; PE-series PDUs typically ship with
teladmin/telpwd. - For models with more than 8 outlets, set the
outlet_counttag on the device. - To label outlets, add tags such as
outlet_1_name: Codecandoutlet_2_name: Display. The PDU’s Telnet interface can’t report the names set in its web interface.
Add the device
- In the portal, go to Devices and select New device.
- Choose the Collector that can reach the device, and set Protocol to ATEN eco PDU.
- Enter the settings below and save. The Collector picks up the new device within seconds.
Tags are set in the Tags section of the device form: select Add tag, then enter the name and value, for example
outlet_count = 16.Readings
These values appear under Device Information on the device page, and can be checked in Room Readiness routines.Commands
Each command is a button on the device page, and can be used in Room Readiness routines.Power readings: each outlet reports its state, current and power, and the PDU its voltage, total power and total current. They show the live draw of whatever is plugged in. Energy estimates in Reports use the Power on and Power standby wattage set on each device’s own record. A reading the model doesn’t measure is left out.
Outlet control: Outlet On, Outlet Off and Outlet Reboot switch an outlet straight away, ignoring any delay set on the PDU. Older firmwares use a different command form; the Collector detects that on the first command and remembers it.